Page 8Installation
Aux Heat (HP)
Range: Y or N
Default: Y
Enables the Auxiliary Heat operation. Typically the
Aux Heat will be heat-strips in a Heat Pump system
2nd Stage Cool
Range: Y or N
Default: N
Enables the 2nd Stage Cool operation
Schedule Enable
Range: Y or N
Default: N
When enabled, the local thermostats scheduler
function is enabled
Recovery Enable
Range: Y or N
Default: N
For Heat Pump Systems - Intelligent setback
recovery is an automatic advance start of heating
to allow the system to be at a setpoint by the
scheduled time, without the use of Aux heating
Delta Settings
The Delta T Setting is the delta, or difference between, the setpoint and current temp for determining when a heat or cool
call comes on. The “delta” is the number of degrees away from setpoint.
H/C Delta
Range: 3 - 15 degrees
Default: 3F (1C)
Sets the minimum separation between heating and
cooling setpoints. Attempts to lower the cooling
below the heating setpoint by this amount will
PUSH the heating setpoint down to maintain this
separation. Same for setting the heating setpoint
above the cooling setpoint, it will PUSH the cooling
setpoint up to maintain this separation.
Heating Delta Stage 1 ON
Range: 1 - 8 degrees
Default: 1
Sets the delta from setpoint that stage 1 heating
starts.
Heating Delta Stage 1 OFF
Range: 0 - 8 degrees
Default: 0
Sets the delta from setpoint that stage 1 heating
stops. Stage 1 turns off at setpoint + Delta Stage 1.
Heating Delta Stage 2 ON
Range: 1 - 8 degrees
Default: 2
Sets the delta from setpoint that stage 2 heating
starts.
Heating Delta Stage 2 OFF
Range: 0 - 8 degrees
Default: 0
Sets the delta from setpoint that stage 2 heating
stops. Stage 2 turns off at setpoint + Delta Stage 2.
Heating Delta Stage 3 ON
Range: 1 - 8 degrees
Default: 3
Sets the delta from setpoint that stage 3 heating
starts.
Heating Delta Stage 3 OFF
Range: 0 - 8 degrees
Default: 0
Sets the delta from setpoint that stage 3 heating
stops. Stage 3 turns off at setpoint + Delta Stage 3.